Specifications: - PS1200 Single Phase
- 20 Year Design Life - Surge Suppression - 2000 Joules - Typical Protection For : Electrical Storms, Lightning Activity and Power Utility Spikes - Let Through Voltage - 150V line-to-neutral - Load Rating - 20A - 240 Volt AC application - Withstands surges to 480 VAC - 50/60 Hertz - Self-healing metallized capacitors - Low losses, 0.5 watt per kVAR - UL Recognized Pressure Sensitive Interrupter - Interrupter for maximum 10,000 amp fault currents - Discharge system to reduce voltage to 50 volts or less within 1 minute of deenergization . Case rupture protection: Internal pressure sensitive devices incorporated to activate at end of life or misapplication. - Operating temperature range of -40° C to +90° C - Flashpoint: + 182 degree C to + 200 degree C - UL 810 Listed File Number- E247765, CE and CSA certified - Values +/- 2% of rating - Hermetically sealed aluminum case with turn plate steel cover - Phenolic insulating bushings - Box size 6" x 6" x 4" - Operating Life: 60,000 hours with 95% survival - General Enclosure: NEMA 3R Indoor/Outdoor - Wire Rating: 600 Volts, THHN or MTW or THWN or AWM, Gasoline & Oil Resistant 11. Caution: - Warning Electrical Shock "Do Not Open" there are NO serviceable parts - Disconnection of Protective Earth Conductor, may impair the performance this product - It is NOT recommended putting any Switches or Fuses In-Line with the Earth Conductor'
|